SUA2200JB

Smart-UPS
APC Smart-UPS 2200VA USB & Serial 100V Black

SUA2200JBSUA2200JB
More Images

APC Smart-UPS, 1980 Watts / 2200 VA,Input 100V / Output 100V, Interface Port DB-9 RS-232, USB, SmartSlot

Includes: User Manual

Standard Lead Time: Usually in Stock

Runtime Chart

Output

Output Power Capacity
1980 Watts / 2200 VA
Max Configurable Power
1980 Watts / 2200 VA
Nominal Output Voltage
100V
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor
up to 5 : 1
Waveform Type
Sine wave
Output Connections
(8) NEMA 5-15R
(2) NEMA 5-20R

Input

Nominal Input Voltage
100V
Input Frequency
50/60 Hz +/- 5 Hz (auto sensing)
Input Connections
NEMA L5-30P
Cord Length
2.44 meters
Maximum Input Current
24A
Input Breaker Capacity
40A

Batteries & Runtime

Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
4.50 hour(s)
RBC™ Quantity
1
Typical Backup Time
at Half Load
24.1 minutes (990 Watts)
Typical Backup Time
at Full Load
6.7 minutes (1980 Watts)
Runtime Chart

Communications & Management

Interface Port(s)
DB-9 RS-232,USB,SmartSlot
Available SmartSlot™ Interface Quantity
1
Control panel
--
Audible Alarm
--
Emergency Power Off (EPO)
Yes

Surge Protection and Filtering

Surge energy rating
510 Joules
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height
432.00 mm
Maximum Width
196.00 mm
Maximum Depth
546.00 mm
Net Weight
51.05 KG
Shipping Weight
60.91 KG
Shipping Height
559.00 mm
Shipping Width
381.00 mm
Shipping Depth
762.00 mm
Color
Black
Units per Pallet
3.00

Environmental

Operating Environment
0 - 40 °C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-3000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
45.00 dBA
Online Thermal Dissipation
275.00 BTU/hr

Conformance

Regulatory Approvals
UL 1778,VCCI
Standard Warranty
2 years repair or replace,optional on-site warranties available,optional extended warranties available
Environmental Compliance
RoHS 7b Exemption