SY48K48H-PD
Price * :  £27,700.00

Symmetra PX
APC Symmetra PX All-In-One 48kW Scalable to 48kW, 400V

SY48K48H-PDSY48K48H-PD
More Images

Hot-scalable power, runtime & distribution in a high-density single frame design. This high-efficiency 3-phase UPS scales as your data center grows up to 48kW/48kVA. Suitable for small & medium data center applications.

Includes: Network Management Card, Start-Up Service

Standard Lead Time: Usually Ships within 2 Weeks

General

Bypass Connection
5 wire (3PH + N + G)
Bypass Voltage Tolerance
+/-10% settable from +/-4/6/8 and 10%
Max Bypass Input Current
80A
Bypass Protection Device
80A

Output

Output Power Capacity
48 kW / 48 kVA
Max Configurable Power
48 kW / 48 kVA
Nominal Output Voltage
230V,400V 3PH
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load
95%
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor
Unlimited
Waveform Type
Sine wave
Output Connections
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full n
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load
95%
Required Output Current Protection
100A
Bypass
Built-in Static Bypass

Input

Nominal Input Voltage
400V 3PH
Input Frequency
40 - 70 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
340 - 477V
Other Input Voltages
380,400,415
Maximum Input Current
98A
Input Breaker Capacity
100A
Input Total Harmonic Distortion
Less than 5% for full load
Type of Input Protection Required
gL fuse

Batteries & Runtime

Battery Type
VRLA
Included Battery Modules
4
Typical recharge time
3 hour(s)
RBC™ Quantity
4
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage
+/-154 V
DC Overcurrent Protection
1008A
Maximum Available Short Circuit Current
4 kA
Efficiency in Battery Operation
94%
End of Discharge Maximum Battery Current
165
Runtime Graph
Curve Part Number(s)
A SY48K48H-PD
B SY48K48H-PD
+ (1)SYCFXR48-9
C SY48K48H-PD
+ (2)SYCFXR48-9
D SY48K48H-PD
+ (3)SYCFXR48-9
E SY48K48H-PD
+ (4)SYCFXR48-9
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Energy Use/Efficiency

Hover over the line on the graph above to view the efficiency at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

Communications & Management

Available SmartSlot™ Interface Quantity
2
Control panel
Multi-function LCD status and control console
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
Yes

Physical

Maximum Height
1991.00 mm
Maximum Width
600.00 mm
Maximum Depth
1070.00 mm
Rack Height
42U
Net Weight
796.00 KG
Shipping Weight
858.00 KG
Shipping Height
2140.00 mm
Shipping Width
848.00 mm
Shipping Depth
1210.00 mm
Color
Black

Environmental

Operating Environment
0 - 40 °C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-999.9 meters
Storage Temperature
-15 - 40 °C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
61.00 dBA
Online Thermal Dissipation
7719.00 BTU/hr
Protection Class
NEMA 1

Conformance

Regulatory Approvals
EN 50091-1,EN/IEC 62040-3,EN/IEC 62040-1-1,FCC Part 15 Class A,VFI-SS-111
Standard Warranty
1 year on-site repair or replace with factory authorized Start-Up
*Except where noted, all prices are Estimated Resale Price (ERP) - Without Tax/VAT. Pricing in other locations and sites may vary.
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.